Permit: T05EL02351

Parcel: 117091690


Addresses:

1016 S 4TH AV #01*

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/09/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/10/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. INSTALL MAIN BREAKER AT SUB-PANEL
2. REMOVE GREEN BOND SCREW ON NEUTRAL BUSS
3. USE PROPER FITTING FOR GFI RECEPTACLE UNDER PANEL
4. REINSTALL HUB AT BOTTOM OF PANEL OR INSTALL 2" CONDUIT AT BOTTOM USING LOCKNUTS & BUSHING.