Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/10/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL MAIN BREAKER AT SUB-PANEL 2. REMOVE GREEN BOND SCREW ON NEUTRAL BUSS 3. USE PROPER FITTING FOR GFI RECEPTACLE UNDER PANEL 4. REINSTALL HUB AT BOTTOM OF PANEL OR INSTALL 2" CONDUIT AT BOTTOM USING LOCKNUTS & BUSHING. |