Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) OWNER REMOVED 2 NON COMPLIANT CIRCUITS. THIS INSPECTION IS FOR SERVICE ONLY AND DOES NOT INCLUDE ANY OTHER INSPECTIONS |
|
| 01/04/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :*CALL FOR FINAL INSPECTION AFTER TEP TIE IN | |
| 12/16/2005 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) TWO GROUND RODS REQUIRED 6'-MINIMUM APART 2) 6'-7" MAX HEIGHT FOR BREAKERS 3) RISER CONDUIT FOR UTILITY POWER TO ENTER AT METER SIDE 4) VERIFY RISER SIZE WITH TEP-CUSTOMER RE-USING ORIGINAL 1". TEP SPECS CALL FOR 2" 5) RISER MUST BE SUPPORTED, USE 1/4" MINIMUM HARDWARE |