Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*CANNOT SPLIT NEUTRAL /GROUNDED CONDUCTOR TIGHTEN LOOSE FITTINGS CONDUCTORS # 4 & LARGER TO HAVE PROTECTION AT FITTING GROUNDING EQUIPMENT CONDUCTOR TO BE ?? ENTIRE LENGTH 250.119 |
|
| 12/21/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*USE CORRECT FITTING AT 1" CONNECTION INTO BOTTOM OF PANEL INSTALL PLASTIC BUSHINGS ON 100 AMP FEED (3) DRYWALL SCREWS NOT ACCEPTABLE FOR OUTSIDE SUPORT UNLESS BRASS OR GALVANIZED (4) TECH SCREW IS NOT AN APROVED GROUNDING TERMINATION |