Permit: T05EL02331

Parcel: 126042820

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/27/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/22/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*CANNOT SPLIT NEUTRAL /GROUNDED CONDUCTOR
TIGHTEN LOOSE FITTINGS
CONDUCTORS # 4 & LARGER TO HAVE PROTECTION AT FITTING
GROUNDING EQUIPMENT CONDUCTOR TO BE ?? ENTIRE LENGTH 250.119
12/21/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*USE CORRECT FITTING AT 1" CONNECTION INTO BOTTOM OF PANEL
INSTALL PLASTIC BUSHINGS ON 100 AMP FEED (3) DRYWALL SCREWS NOT ACCEPTABLE FOR OUTSIDE SUPORT UNLESS BRASS OR GALVANIZED (4) TECH SCREW IS NOT AN APROVED GROUNDING TERMINATION