Permit: T05EL02328

Parcel: 11006159B

Inspection Status: Closed

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/24/2007 ELECTRIC - FINAL Closed
07/26/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 413 SUBJECT TO OTHER INSPECTIONS
07/24/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED CHECK #2517 FOR $108.00 UNSCHEDULED INSP.
OK UNIT 411
07/24/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. KITCHEN CIRCUITS HAVE OPEN GROUND -- GFCI NOT WORKING.
2. USE CORRECT SIZED BREAKER AMPACITY FOR CONDUCTOR SIZE.
3. CORRECTLY IDENTIFY CONDUCTOR COLORS
4. IDENTIFY CIRCUITS AT DIRECTORY
5. USE APPROVED CONNECTOR AT HOOD
6. CLEAN TRASH OUT OF BOTTOM OF PANEL
7. UNIT IS OCCUPIED.
07/23/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/21/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/18/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
413
1. HOOD TO HAVE A CONNECTOR FOR NM CABLE.
2. USE APPROVED MANUFACTURERS COVER.

411
1. MISSING LIGHT
2. UNIT OCCUPIED
07/14/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ELECTRICIAN NOT AVAILABLE TO INSPECT WITH AS PREVIOUSLY ARRANGED.
06/19/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK UNIT #404
06/16/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
#404
1. IF BACK FED BREAKER IS USED FOR MAIN IT MUST BE HELD IN PLACE WITH MANUFACTURERS HOLD DOWN. 408.16
06/09/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/06/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #414
05/22/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/07/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20
2. 2 CIRCUITS TO SERVE COUNTERTOPS 210.52
3. CLEAN FOREIGN MATERIAL FROM PANEL
4. PLEASE REVISE PANEL SCHEDULE
02/01/2006 ELECTRIC - FINAL Cancelled IVRS - RI canceled