Inspection History Details
Inspection Status: Closed
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | ELECTRIC - FINAL | Closed | ||
| 07/26/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 413 SUBJECT TO OTHER INSPECTIONS |
|
| 07/24/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECEIVED CHECK #2517 FOR $108.00 UNSCHEDULED INSP. OK UNIT 411 |
|
| 07/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. KITCHEN CIRCUITS HAVE OPEN GROUND -- GFCI NOT WORKING. 2. USE CORRECT SIZED BREAKER AMPACITY FOR CONDUCTOR SIZE. 3. CORRECTLY IDENTIFY CONDUCTOR COLORS 4. IDENTIFY CIRCUITS AT DIRECTORY 5. USE APPROVED CONNECTOR AT HOOD 6. CLEAN TRASH OUT OF BOTTOM OF PANEL 7. UNIT IS OCCUPIED. |
|
| 07/23/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/21/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/18/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 413 1. HOOD TO HAVE A CONNECTOR FOR NM CABLE. 2. USE APPROVED MANUFACTURERS COVER. 411 1. MISSING LIGHT 2. UNIT OCCUPIED |
|
| 07/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ELECTRICIAN NOT AVAILABLE TO INSPECT WITH AS PREVIOUSLY ARRANGED. |
|
| 06/19/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK UNIT #404 |
|
| 06/16/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* #404 1. IF BACK FED BREAKER IS USED FOR MAIN IT MUST BE HELD IN PLACE WITH MANUFACTURERS HOLD DOWN. 408.16 |
|
| 06/09/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/06/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK #414 |
|
| 05/22/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/07/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 2. 2 CIRCUITS TO SERVE COUNTERTOPS 210.52 3. CLEAN FOREIGN MATERIAL FROM PANEL 4. PLEASE REVISE PANEL SCHEDULE |
|
| 02/01/2006 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |