Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05EL02328

Parcel: 11006159B

Inspection Status: Closed

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/24/2007 ELECTRIC - INTERMEDIATE Closed
01/26/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/17/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTRACTOR THAT WAS STATED TO BE DOING WORK HAS INFORMED ME HE HAS NOT AND IS NOT PERFORMING WORK DONE. NO FURTHER INSPECTIONS UNTIL WE MEET WITH QUALIFIED CONTRACTOR WHO WILL DO THE WORK
ALSO, CALL IN COMBO PERMIT.

DO NOT PROCEED WITH ANY FURTHER WORK
01/09/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. INSTALL ALL STRANDS UNDER TERMINAL LUGS
2. STRAP NM CABLES WITHIN 12" OF BOXES
3. GROUND METAL BOXES
4. OPEN WALL IN LAUNDRY AS NEEDED
5. CALL INSPECTIONS ON COMBINATION PERMITS
6. CEASE OCCUPANCY OF ALL UNITS UNTIL UNITS RECEIVE INSPECTION.
07/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 403 ROUGH SUBJECT TO OTHER INSPECTION
06/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH #401
05/22/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELEC. FINAL UNIT #416
02/23/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 413, 414, 415
02/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK 402,404,405,411,412,416
02/01/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/03/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio NO WORK PROGRESDS A REFEE HAS BEEN ACCESSED PER ADMINISTRATIVE CODES
12/20/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK # 4 EXCEPT AT PANEL
12/16/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) WE HAVE BOX OVER FILL
2) PROTECT CABLES AT STUDS
3) FINISH PREVIOUS ITEMS
12/15/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*NEED CITY STAMP
NO FURTHER INSPECTION UNTIL STAMPED.
11/28/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
UNIT #4: 1) GROUND BOXES
2) SECURE NM CABLE AT STUB POINT
3) CABLE SHEATHING TO ENTER 1/4" INTO BOX
4) PROTECT CONDUCTOR FROM SCREWS INSIDE OF BOX 314.43
5) TIGHTEN LOOSE FITTINGS
6) SEPERATE GROUNDS FROM NEUTRAL AND PROVIDE A GROUND PATH
7) PLEASE VERIFY BOX FILL PER 314.16
8) SECURE CABLES TO BOX 312.5
9) WAITING ON PLANS REVISION AND CITY STAMP
11/25/2005 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
11/22/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*