Inspection History Details
Inspection Status: Closed
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | ELECTRIC - INTERMEDIATE | Closed | ||
| 01/26/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/17/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTRACTOR THAT WAS STATED TO BE DOING WORK HAS INFORMED ME HE HAS NOT AND IS NOT PERFORMING WORK DONE. NO FURTHER INSPECTIONS UNTIL WE MEET WITH QUALIFIED CONTRACTOR WHO WILL DO THE WORK ALSO, CALL IN COMBO PERMIT. DO NOT PROCEED WITH ANY FURTHER WORK |
|
| 01/09/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL ALL STRANDS UNDER TERMINAL LUGS 2. STRAP NM CABLES WITHIN 12" OF BOXES 3. GROUND METAL BOXES 4. OPEN WALL IN LAUNDRY AS NEEDED 5. CALL INSPECTIONS ON COMBINATION PERMITS 6. CEASE OCCUPANCY OF ALL UNITS UNTIL UNITS RECEIVE INSPECTION. |
|
| 07/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 403 ROUGH SUBJECT TO OTHER INSPECTION |
|
| 06/09/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH #401 |
|
| 05/22/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELEC. FINAL UNIT #416 |
|
| 02/23/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 413, 414, 415 |
|
| 02/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK 402,404,405,411,412,416 | |
| 02/01/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/03/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio NO WORK PROGRESDS A REFEE HAS BEEN ACCESSED PER ADMINISTRATIVE CODES |
|
| 12/20/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK # 4 EXCEPT AT PANEL | |
| 12/16/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) WE HAVE BOX OVER FILL 2) PROTECT CABLES AT STUDS 3) FINISH PREVIOUS ITEMS |
|
| 12/15/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*NEED CITY STAMP NO FURTHER INSPECTION UNTIL STAMPED. |
|
| 11/28/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* UNIT #4: 1) GROUND BOXES 2) SECURE NM CABLE AT STUB POINT 3) CABLE SHEATHING TO ENTER 1/4" INTO BOX 4) PROTECT CONDUCTOR FROM SCREWS INSIDE OF BOX 314.43 5) TIGHTEN LOOSE FITTINGS 6) SEPERATE GROUNDS FROM NEUTRAL AND PROVIDE A GROUND PATH 7) PLEASE VERIFY BOX FILL PER 314.16 8) SECURE CABLES TO BOX 312.5 9) WAITING ON PLANS REVISION AND CITY STAMP |
|
| 11/25/2005 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 11/22/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |