Permit: T05EL02328

Parcel: 11006159B

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
02/23/2006 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
NOT REQ'D
02/06/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
02/01/2006 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1. SECURE NM CABLE TO BOX AND FILL UNUSED OPENING 402, 404
2. PROVIDE GROUND PATH 402, 404, 405
3. BOX FILL IN LAUNDRY 402
4. CABLE SHEATING TO ENTER 1/4" INTO BOX
5. BOXES TO BE FAN RATED ALL UNITS
6. GROUND METAL BOXES
7. INSTALL PLASTER RINGS
8. PROTECT CABLES AT STUDS
9. SUPPORT NM CABLES ABOVE PANEL
01/03/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
12/20/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
12/15/2005 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
11/22/2005 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*PLANS TO REFLECT WORK BEING DONE
PLEASE OPEN ONE SIDE OF WALLS TO INSPECT