Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* TOM LOPEZ TO TAPE HOT CONDUCTOR IN PNL 204 BLK. 211 - GARBAGE DSH; INSULATE 203 - CLEAN PNL , TAPE NEUT, CLEAN BOT OF PN 204 - UNGROUND CONDUTOR, TAPE VENT |
|
| 07/06/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK #202 #211 1. FINISH GARBAGE DISPOSAL AT COUNTER 2. TAPE TO INSULATE NEUTRAL #203 1. CLEAN BUSS OF FOREIGN MATERIAL 2. TAPE TO ISOLATE NEUTRAL 3. CLEAN BOTTOM OF PANEL OF TRASH. #204 1. CURRENTLY IDENTIFY UNGROUNDED CONDUCTORS 2. TAPE TO INSULATE NEUTRAL 3. SMOKE DETECTOR TO BE 36" FROM DUCT |
|
| 06/28/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) MOVE SD'S AS DISCUSSED 2) SEAL ALL UNUSED OPENINGS, USE THE PROPER VERTICALS 3) RECEPTACLE COVER, FINISH ALL TRIM, ID CIRCUITS, USE FLASH RINGS AT LAUNDRY WHRE PLYWOOD IF BOX IS 1/4" OR MORE DEEP INTO OK ELECTRIC FINAL 10, 3, 23 AND 22 |
|
| 06/23/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 212 FOR ROUGH ELECTRIC OK 213 FOR FINAL |
|
| 06/19/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SUPPORT MC CABLES ABOVE PANEL. 2. LOOSE FITTINGS. 3. FILL UNUSED OPENING IN PANEL AND JUNCTION BOXES. 4. SMOKE DETECTORS TO BE 3' FROM DUCT OR VENT. 5. SUPPORT NM CABLE 12" |
|
| 06/16/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK UNITS 215 & 216 |
|
| 06/09/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* #212 COVERED WITHOUT INSPECTION 1. FINISH PREVIOUS ITEMS. |
|
| 01/04/2006 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |