Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/27/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. PROPERLY INSTALL BOND CLAMPS CONDUCTORS ONLY UNDER TERMINATION LUG. ALSO ON INTERIOR SIDE OF UNION 2. ONLY 2 CONDUCTORS ALLOWED UNDER A SPLIT BOLT CONNECTION BY LISTING |
|
| 01/24/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/17/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*PER TEP METER BASE NOT TO EXCEED 6'3" TO CENTER. INSTALL METAL ADDRESS LABEL PER I.R.C & TEP EXPOSE GROUND RODS I CAN'T LOCATE WHERE YOU BONDED THE GAS PIPING HIGHEST BREAKER IS NOT TO EXCEED 6'6" ABOVE FINISHED GRADE |