Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/03/2006 ELECTRIC - INTERMEDIATE Approved
12/13/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK TO ENERGIZE SERVICE
12/09/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1. INSTALL LOCKNUTS ON RACEWAY FOR SUB-PANEL
2. SEPERATE NEUTRAL AND GROUNDS IN SUB-PANEL
3. STRAP RISER TO STRUCTURE
12/08/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*RODS ARE INCORRECTLY TERMINATED AT GROUNDING ELECTRODE
TERMINATE GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO NEUTRAL BUS AT SERVICE EQUIPMENT.
INSTALL 2 1/2" BONDING BUSHING AT RISER AND BOND TO EQUIP. GROUNDING BUS.
LABEL ADDRESS PER T.E.P & I.R.C REQUIEMENT
BURY GROUNDING ELECTRODE CONDUCTOR.