Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 12/13/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK TO ENERGIZE SERVICE | |
| 12/09/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. INSTALL LOCKNUTS ON RACEWAY FOR SUB-PANEL 2. SEPERATE NEUTRAL AND GROUNDS IN SUB-PANEL 3. STRAP RISER TO STRUCTURE |
|
| 12/08/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*RODS ARE INCORRECTLY TERMINATED AT GROUNDING ELECTRODE TERMINATE GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO NEUTRAL BUS AT SERVICE EQUIPMENT. INSTALL 2 1/2" BONDING BUSHING AT RISER AND BOND TO EQUIP. GROUNDING BUS. LABEL ADDRESS PER T.E.P & I.R.C REQUIEMENT BURY GROUNDING ELECTRODE CONDUCTOR. |