Permit: T05EL02288

Parcel: 133041180


Addresses:

9236 E CALLE KUEHN

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/18/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/13/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :A GAS BOND IS NEEDED
BOND BUSHINGS NEEDED ON SERVICE NIPPLE 250.92
SEALING DEVICE NEEDED FOR ENTRANCES ABOVE CURRENT CARRING CONDUCTORS
EXTENTION CORDS NOT ALLOWED FOR PERMANENT WIRING
PROTECT CONDUCTORS FROM SHARP METAL EDGES
OK TO CLEAR CALLED ANNA TEP
01/12/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*