Permit: T05EL02285

Parcel: 12213264A


Addresses:

4202 E PIMA ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T05EL02285

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
11/22/2005 ELECTRIC - RECONNECT Approved
11/18/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
NO COMPLIANCE WITH NOTES FROM PREVIOUS INSPECTOR
EXPOSE GROUND RODS FOR INSPECTION
LOOSE FITTINGS
GROUND TAPS NOT SECURELY SUPPORTED TO WALL-NOT PROPER METHOD
RISER SHOULD BE SUPPORTED WITH 1/4" BOLTS-USE 2 HOLE STRAPS
VERIFY C-11 LICENSED CONTR. NAME PH #
CHANGE PERMIT DESCRIPTION TO SERVICE UPGRADE,
11/15/2005 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*THIS IS A SERVICE UPGRADE
A NEW ELECTRICAL GROUNDING SYSTEM IS REQUIRED 2 GROUND RODS 6' MIN APART. A WTER AND A GAS BOND
PLEASE TIGHTEN LOOSE FITTINGS
TIGHTEN CONDUCTOR TERMINATIONS
WE HAVE BARE CONDUCTORS, INSULATION TO BE COMPLETE.
IDENTIFY NEUTRAL CONDUCTOR AT WEATHER HEAD.
LABELING OF BREAKERS TO BE PERMANENT
A PERMANENT METAL ADDRESS LABEL IS NEEDED
SUPPORT RISER SECURELY TO STRUCTURE.