Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T05EL02285
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2005 | ELECTRIC - RECONNECT | Approved | ||
11/18/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NO COMPLIANCE WITH NOTES FROM PREVIOUS INSPECTOR EXPOSE GROUND RODS FOR INSPECTION LOOSE FITTINGS GROUND TAPS NOT SECURELY SUPPORTED TO WALL-NOT PROPER METHOD RISER SHOULD BE SUPPORTED WITH 1/4" BOLTS-USE 2 HOLE STRAPS VERIFY C-11 LICENSED CONTR. NAME PH # CHANGE PERMIT DESCRIPTION TO SERVICE UPGRADE, |
|
11/15/2005 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :*THIS IS A SERVICE UPGRADE A NEW ELECTRICAL GROUNDING SYSTEM IS REQUIRED 2 GROUND RODS 6' MIN APART. A WTER AND A GAS BOND PLEASE TIGHTEN LOOSE FITTINGS TIGHTEN CONDUCTOR TERMINATIONS WE HAVE BARE CONDUCTORS, INSULATION TO BE COMPLETE. IDENTIFY NEUTRAL CONDUCTOR AT WEATHER HEAD. LABELING OF BREAKERS TO BE PERMANENT A PERMANENT METAL ADDRESS LABEL IS NEEDED SUPPORT RISER SECURELY TO STRUCTURE. |