Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02280

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio SEPERATE NEUTRALS AND GROUNDS IN SUB PANELS
PROVID ACCESS TO WATER AND GAS BOND
PAY REINSPECTION FEE
SMALL SUB PANEL WILL NEED EQUIPMENT GROUND
02/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*NEED 3/0 FOR 200 AMP SUB PANEL
SEPERATE GROUNDS AND NEUTRALS IN BOTH SUB PANELS
CORRECTLY IDENTIFY AL BRANCH CKT'S
BOND METAL PIPE SYSTEMS TO SERVICE-WATER, GAS, AND DRAIN
SEAL HOLE IN ROOF & PROVIDE LADDER FOR FLASHING INSPECTION
CHECK WIRING METHOD-NEC 518.4 AND PROVIDE JOB PLANS
01/11/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1) INSTALL FLASHING CORRECTLY AND SEAL ROOF PENETRATIONS (GUY)
2) CORRECTLY IDENTIFY PANEL DIRECTORY
3) INSTALL ADDRESS LABEL FOR SERVICE
4) TIGHTEN ALL GROUNDING BUSHINGS AND SET SCREWS
5) CLOSE ALL UNUSED OPENINGS IN EQUIPMENT
6) EXISTING PANEL IS NOW A SUB-PANEL AND NEEDS 3/0 CU PHASE CONDUCTORS WITH AN EQUIPMENT GROUND-SEPERATE THE GROUNDS AND NEUTRALS AND INSTALL DEAD FRONT COVER
7) BOND ALL METAL PIPE SYSTEMS TO SERVICE
8) ADD ANY NEW BRANCH CKTS TO PERMIT FOR INSPECTION
9) L.B. BY DOOR NOT CONNECTED AND IS OPEN