Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 12/15/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK TO ENERGIZE SERVICE FOR SWITCHOVER | |
| 11/30/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210$ 1) INSTALL FLASHING FOR MAST 2) INSTALL SERVICE ENTRANCE CONDUCTORS 3) THREAD MAST ALL THE WAY INTO HUB 4) BOND SERVICE TO BLDG PIPES (GAS, WATER AND WASTE) 5) INSTALL MAIN GROUNDING ELECTRODE TO SERVICE |