Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2005 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 12/20/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999*FINISH PREVIOUS ITEMS |
|
| 12/15/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/12/2005 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1. USE AN APPROVED FITTING WITH LB - CHASE NIPPLE NOT APPROVED 2. SEAL ENTRANCES ABOVE CURRENT CARRIER PARTS 3. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 4. BOND GROUND BAR TO ENCLOSURE 5. SEPARATE GROUNDING AND GROUNDED CONDUCTORS 6. A MAIN DISCONNECTING MEANS IS NEEDED AT 2ND STRUCTURE 225.31 & 32 7. CONDUIT NOT TO BE A SUPPORT FOR VDV CABLES 8. STRAP GROUNDING TO STRUCTURE |
|
| 11/30/2005 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :*OK TO CLEAR # 1 ONLY INC. 1) RECALL FOR CROSSOVER CONNECTION |
|
| 11/23/2005 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :*STRAP GROUDING EELCTRODE CONDUCTOR TO BUILDING PLEASE VERIFY WATER BONDING 250.104 ENTRANCES ABOVE CURRENT CARRING PARTS TO USE AN APPROVED SEALING DEVICE CONDUCTORS # 8 AND LARGER TO BE STRANDED IN RACEWAYS 300.3 PLEASE LABEL UNITS CORRECTLY SECURELY ATTACH RISER TO STRUCTURE GROUNDING ELECTRODE CONDUCTOR TO BE SIZED PER 250. 16 GROUNDING ELECTRODE TO TERMINATE AT GROUNDED TERMINAL 25O.24 UNDERGROUND CONDUIT TO BE RUN ?? FOR POWER RELEASES |