Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2005 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/21/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*GROUND BAR IN AT( INSIDE) LEFT PANEL NOT GROUND PROPERLY ED NO NEUTRAL FEEDER AT LARGER PANEL ON RIGHT INSTALL GROUND TAP ( SPLIT BOLT) OUTSIDE OF SMALLER DISCONNECT AT SERVICE TO ENSURE THAT GROUND WAILL NOT BE DISCONNECTED TO LARGER DISCONNECT IN THE EVENT THE SMALLER ONE IS REMOVED. ADDRESS LABELS MUST BE SCREWED OR RIVITED TO COVERS. AT SERVICE |
|
| 11/14/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |