Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/18/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*CLEAN PAINT OFF GAS LINE WHERE GAS BOND CLAMP IS ATTACHED INSTALL WATER BOND AND BOND TO ELECTRODE CONDUCTOR ( ABOVE DIELECTRIC UNION) INSTALL ANTI OXIDATION PASTE ON ALL ALUM. TERMINATIONS ( RANGE CIRCUIT) INSTALL MISSING MACHINE SCREW AT DEAD FRONT COVER DRIVE GROUND RODS FLUSH OR BELOW FINISHED GRADE. |