Permit: T05EL02245

Parcel: 111070160


Addresses:

3434 E WATER ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02245

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
CELL -- 318-4346
JIM -- 603-0336
11/09/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*MAIN SERVICE:
BOND ALL DISCONNECT ENCLOSERS
PLEASE FILL UNUSED OPENINGS AT DISCONNECT 25,26-30
SUPPORT CONDUITS BELOW DICONNECTS
INSTALL BUSHING PER 300 AND HOUSING INSPECTOR REQUEST
UNIT #1
INSTALL GROUND BAR AT SUBPANEL
UNIT # 3 NO WORK
UNIT #8
A GROUNDING ELECTRODE SYSTEM IS NEEDED
IDENTIFY GROUNDED AND GROUNDING CONDUCTORS
ISOLATE GROUNDED CONDUCTOR
OK AT UNIT # 15,34
11/08/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*UNABLE TO LOCATE ALL WORK UPGRADED
CALL TO MEET CONTRACTOR
ALSO # 50 NPO INVOLVED