Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL02245
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* CELL -- 318-4346 JIM -- 603-0336 |
|
| 11/09/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*MAIN SERVICE: BOND ALL DISCONNECT ENCLOSERS PLEASE FILL UNUSED OPENINGS AT DISCONNECT 25,26-30 SUPPORT CONDUITS BELOW DICONNECTS INSTALL BUSHING PER 300 AND HOUSING INSPECTOR REQUEST UNIT #1 INSTALL GROUND BAR AT SUBPANEL UNIT # 3 NO WORK UNIT #8 A GROUNDING ELECTRODE SYSTEM IS NEEDED IDENTIFY GROUNDED AND GROUNDING CONDUCTORS ISOLATE GROUNDED CONDUCTOR OK AT UNIT # 15,34 |
|
| 11/08/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*UNABLE TO LOCATE ALL WORK UPGRADED CALL TO MEET CONTRACTOR ALSO # 50 NPO INVOLVED |