Permit: T05EL02236

Parcel: 113072250

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/19/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/14/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*NEED TO BOND RACEWAY TOGETHER WHERE THEY ENTER AND EXIT AT GUTTER REGULAR LOCKNUT ARE NOT ALLOWED
NEED TO BOND GUTTER.
11/10/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NOTE: FINISH SERVICE-THEN CALL IN FOR FINAL