Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 11/23/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*INSTALL GAS & WATER BOND TO MAIN SERVICE INSTALL # 4 GROUNDING ELECTRODE CONDUCTOR ( # 5 IS TOO SMALL FOR EXPOSED CONDUCTOR) INSTALL PLASTIC BUSHING @ 1" E.M.T CONNECTOR INSTALL EQUIP. GROUNDING CONDUCTOR ON FEED TO EXISTING EQUIPMENT INSTALL CORRECT SIZED BREAKER SEE AMPACITY CHART 310.16 ( 75 DEGREE COL.) FOR ALUMINUM CONDUCTOR |