Permit: T05EL02234

Parcel: 126100870


Addresses:

4401 E 7TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/28/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/23/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*INSTALL GAS & WATER BOND TO MAIN SERVICE
INSTALL # 4 GROUNDING ELECTRODE CONDUCTOR ( # 5 IS TOO SMALL FOR EXPOSED CONDUCTOR)
INSTALL PLASTIC BUSHING @ 1" E.M.T CONNECTOR
INSTALL EQUIP. GROUNDING CONDUCTOR ON FEED TO EXISTING EQUIPMENT
INSTALL CORRECT SIZED BREAKER SEE AMPACITY CHART 310.16 ( 75 DEGREE COL.)
FOR ALUMINUM CONDUCTOR