Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL02221
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*SERVICE REPAIR BUST SECTIONS REPLACED BY CORONA ELECT, TORQUE TO MANUFACTURERS SPEC'S,PARTS PROVIDED BY JON LOCKHART. REP EATON CUTLER HAMMER |