Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/06/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210*DRIVE GROUND RODS FLUSH BURY OR ATTACH TO BUILDING MAIN GROUNDING ELECTRODE CONDUCTOR BOND WATER AND GAS PIPES TO SERVICE USE SUN LIGHT RESISTANT SERVICE WIRE IDENTIFY FEEDER GROUNDED CONDUCTOR INSTALL COVERS FOR OPEN BREAKER SPACES DIFFERENT SIZES OF GROUND NOT ALLOWED ON SPLIT IN J BOX INSTALL ADDRESS LABEL ON SERVICE. |