Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/13/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/06/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*DRIVE GROUND RODS FLUSH
BURY OR ATTACH TO BUILDING MAIN GROUNDING ELECTRODE CONDUCTOR
BOND WATER AND GAS PIPES TO SERVICE
USE SUN LIGHT RESISTANT SERVICE WIRE
IDENTIFY FEEDER GROUNDED CONDUCTOR
INSTALL COVERS FOR OPEN BREAKER SPACES
DIFFERENT SIZES OF GROUND NOT ALLOWED ON SPLIT IN J BOX
INSTALL ADDRESS LABEL ON SERVICE.