Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL02205
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2011 | ELECTRIC - FINAL | Approved | ||
11/03/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE ON SITE, MAKE SURE SOMEONE WILL BE AVAILABLE WHEN MAKING INSPECTION REQUEST |
|
10/06/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
11/03/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*CONENCT RANGE NEUTRAL TO INSULATED ( WHITE) CONDUCTOR, AND NOT TO EQUIPMENT GROUND AT BACK DOOR J-BOX ( EXTERIOR) CAP UNUSED NEUTRAL AND VERIFY CORRECT POLARITY TO EXISISTING BRANCH CKT'S @ BACK DOOR J-BOX ( INSIDE) REMOVE MAIN GROUNDING ELECTRODE CONDUCTOR FROM BRANCH CKT J-BOX AND RUN DIRECTLY TO SERVICE DISCONNECT ENCLOSER ( J-BOX ALREADY GROUNDED THROUGH NIPPLE AND IS NOT PART OF GROUNDING ELECTRODE SYSTEMS. |
|
11/01/2005 | ELECTRIC - FINAL | Not ready for Inspection |