Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/22/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/16/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) INSTALL ONLY APPROVED BREAKERS PER PANEL MANUFACTURERS LABEL IN PANEL
2) SUPPORT 1 1/4" EMT PER NEC CHECK EMT CONNECTOR AT LB @ PARAPET ( IT LOOKS ASKEW & LOOSE)
3) INSTALL PROPER SCREWS AT DEAD FRONT COVER ( SHEET METAL SCREWS ARE NOT ALLOWD PER NEC ) 4) INSTALL MISSING, SCREWS AT HINGE 5) PLEASE ON FUTURE JOBS DO NOT ATTACH TO THE PLYWOOD. REMOVE AND ATTACH TO STRUCTURE & ?? ADOBE THERE ARE ADEQUATE EPOXY ANCHORS THAT WILL GIVE YOU GOOD SUPPORT ( IN THIS CASE PAINT OR TREAT EXISTING PLYWOOD) 6) EXISTING PVC LOOKS TO BE SCH. 40 PLEASE REPLACE WITH PIPE OR SCH. 80 PVC.
NOTE: INSPECTION IS IMCOMPLETE DUE TO ME NOT BEING ABLE TO ACCESS PANEL