Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05EL02187

Parcel: 131080750


Addresses:

5902 E 25TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/10/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*OK TO CLEAR INC
CALLED IN TO RAY
11/03/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*COMPLEATLY IDENTIFY UNGROUNDED CONDUCTOR 200.7
BREAKER NOT LISTED FOR MULTIPOLE TERMINATIONS/ PLEASE PROVIDE MANUFACTURERS INSTRUCTIONS FOR SURGE ARRESTOR.