Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK TO CLEAR INC CALLED IN TO RAY |
|
| 11/03/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*COMPLEATLY IDENTIFY UNGROUNDED CONDUCTOR 200.7 BREAKER NOT LISTED FOR MULTIPOLE TERMINATIONS/ PLEASE PROVIDE MANUFACTURERS INSTRUCTIONS FOR SURGE ARRESTOR. |