| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/03/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE VERIFY 2ND GROUND ROD 2. WHERE IS GAS BOND 3. LABEL BREAKERS 4. CORRECLTY IDENTIFY UNGROUNDED CONDUCTOR 5. BOND SERVICE ENCLOSURE 6. SEPARATE GROUNDING EQUIPMENT CONDUCTORS |