Permit: T05EL02158

Parcel: 117030330

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02158

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*INSTALL # 8 ?? @ J BOX GROUND FOR 100AMP EQUIPMENT GROUND NEC. 250.122
12/16/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*USE SUNLIGHT RESISTANT SERVICE WIRE FOR MAST
PROVIDE BUSHINGS FOR # 4 AND LARGER WIRE
BOND METAL WATER PIPE TO SERIVCE
IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD
GROUND FEEDER J-BOX
DO A BETTER JOB OF IDENTIFYING GUEST HOUSE MAIN
STRAP CONDUIT GOING TO J BOX
MAKE SURE GROUNDING ELECTRODES FOR BOTH SERVICES ARE CONNECTED TOGETHER.