Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/24/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/20/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MUST USE ONLY SQUARE D BREAKERS IN PANEL
2) MUST ID PANEL BREAKERS
3) GROUND RODS TO BE DRIVEN TO GRADE OR BELOW
4) 40 AMP BREAKER HAS #10 WIRE ON IT-CHANGE TO 30 AMP