Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/20/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST USE ONLY SQUARE D BREAKERS IN PANEL 2) MUST ID PANEL BREAKERS 3) GROUND RODS TO BE DRIVEN TO GRADE OR BELOW 4) 40 AMP BREAKER HAS #10 WIRE ON IT-CHANGE TO 30 AMP |