Permit: T05EL02139

Parcel: 123022540

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/17/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*CANNOT CLEAR INCREASE ON RECON PERMIT
OK TO CLEAR RECONNECT. ( PER RAY NOT TO CLEAR YET-JK)
11/02/2005 ELECTRIC - FINAL Denied SERVICE RACEWAY NOT PROPERLY GROUNDED
PROVIDE BUSHINGS FOR SERVICE CONDUCTORS
MAIN GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS ( NOT JUMPER )
NEED TO BOND WATER AND GAS PIPES
DRIVE GROUND RODS FLUSH
PROVIDE ACCESS INTO HOME