Permit: T05EL02136

Parcel: 108240850


Addresses:

2494 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02136

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/27/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROVIDE SERVICE DISCONNECT PER 2002 NEC 230.70
2. J-BOX AND EMT THAT ENCLOSE GROUNDED ELECTRODE CONDUCTORS NEED TO BE MADE ELECTRICALLY CONTINUOUS NEC 250.64 (E)
3. SERVICE RACEWAYS NEED TO BE INSTALLED PER NEC 250.92 (B)
4. PROVIDE PROPER WORKING CLEARANCE FOR EQUIPMENT NEC 110.26
5. SIZE ALL SERVICE (LINESIDE) BONDING CONDUCTORS PER NEC 250.102 (C) AND GROUND TAP PER NEC 250.64(D)
6. IDENTIFY SERVICE DISCONNECTS NEC 230.72(A)
7. SELF TAP SCREWS NOT ALLOWED FOR GROUND LUGS
8. INSTALL OVERCURRENT PROTECTION FOR FEEDERS ON SECONDARY SIDE OF TRANSFORMER FOR CHILLER, MAX 60 AMP.
9. SAME SIZE CONDUCTORS UNDER LUGS
10. GROUND MRI GUTTER
11. SECURE TRANSFORMERS TO FLOOR NEC 300
12. TIGHTEN ALL GROUNDING BUSHING SET SCREWS & LUGS