Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL02136
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/27/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
02/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROVIDE SERVICE DISCONNECT PER 2002 NEC 230.70 2. J-BOX AND EMT THAT ENCLOSE GROUNDED ELECTRODE CONDUCTORS NEED TO BE MADE ELECTRICALLY CONTINUOUS NEC 250.64 (E) 3. SERVICE RACEWAYS NEED TO BE INSTALLED PER NEC 250.92 (B) 4. PROVIDE PROPER WORKING CLEARANCE FOR EQUIPMENT NEC 110.26 5. SIZE ALL SERVICE (LINESIDE) BONDING CONDUCTORS PER NEC 250.102 (C) AND GROUND TAP PER NEC 250.64(D) 6. IDENTIFY SERVICE DISCONNECTS NEC 230.72(A) 7. SELF TAP SCREWS NOT ALLOWED FOR GROUND LUGS 8. INSTALL OVERCURRENT PROTECTION FOR FEEDERS ON SECONDARY SIDE OF TRANSFORMER FOR CHILLER, MAX 60 AMP. 9. SAME SIZE CONDUCTORS UNDER LUGS 10. GROUND MRI GUTTER 11. SECURE TRANSFORMERS TO FLOOR NEC 300 12. TIGHTEN ALL GROUNDING BUSHING SET SCREWS & LUGS |