Permit: T05EL02131

Parcel: 130121710


Addresses:

3765 E 33RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/29/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/25/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*NOTES
INSTALL BOND BUSHING AT 1" CONDUIT TERM. INTO SERVICE & SUPPORT CONDUIT.
BOND NEUTRAL IN SERVICE PANEL.
CONDUCTORS FROM METER BASE TO PANEL TO SMALL SHOULD BE # 2
10/19/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* COOLER NOT WIRED PER CODE, INSTALL W/P BOX, RECEPT, COVER.
INSTALL SMOKE DETECTORS IN SLEEPING AREAS.
OUTSIDE RECEPT. BY WATER HTR NEED TO BE GFI PROTECTED WITH W/P COVER
PANEL BELOW METER WAS REPLACED RECENTLY. NOT INSTALLED PROPERLY, CANNOT OPEN COVER DUW TO WRONG TYPE SCREWS FOR HUB AT T & P. ALSO NOT GROUNDED PROPERLY, INSTALL GROUNDING ELECTRODE SYSTEM, BOND WATER & GAS PIPING.
REMOVE 240 V OUTLET BELOW PANEL OR INSTALL PER CODE.