Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/22/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245$CORRECTIONS NEEDED MAX FUSE FOR A.C ( GET PERMIT) IS TO BE 35 AMPS NEED IN USE COVER AND GFI PROTECTION FOR 20 AMP EXTERIOR OUTLET ( BY RV OUTLET) MAX BREAKER FOR SUB PANEL FEED IS 40 AMP FOR # 6 CLAD AND 50 AMP FOR # 4 ( CHECK WIRE SIZE) REPAIR /REPLACE CRACKED HUB BLANK INTOP OF PANEL |