Permit: T05EL02128

Parcel: 122171480


Addresses:

3344 E CAMDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/14/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/22/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245$CORRECTIONS NEEDED
MAX FUSE FOR A.C ( GET PERMIT) IS TO BE 35 AMPS
NEED IN USE COVER AND GFI PROTECTION FOR 20 AMP EXTERIOR OUTLET ( BY RV OUTLET)
MAX BREAKER FOR SUB PANEL FEED IS 40 AMP FOR # 6 CLAD AND 50 AMP FOR # 4 ( CHECK WIRE SIZE)
REPAIR /REPLACE CRACKED HUB BLANK INTOP OF PANEL