Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2005 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/16/2005 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* | |
| 11/14/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/20/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL SMOKE DETECTORS IN BEDROOMS 2) WIRING IN FRONT ABOVE DOOR OUTSIDE NOT PER CODE CANNOT SPLICE WIRING BACK OF LIGHT WITHOUT J-BOX 3) REPAIR COOLER RECEPTACLE IN BACK, MUST BE W/P OR ABANDON 4) NEW 125 AMP PANEL INSTALLED BELOW EXISTING 60 AMP METER BASE, NOT APPROVED, METER BASE AND ASSOCIATED WIRING, RISER CONDUCTORS MUST ALL BE LISTED FOR 125 AMP. IF THE SERVICE IS UPGRADED TO 125 AMP OBTAIN PERMIT FOR SUCH |