Permit: T05EL02106

Parcel: 115042000


Addresses:

1217 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02106

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CORRECTLY IDENTIFY PANEL DIRECTORY
2) PROVIDE ACCESS TO ROOF AND INTERIOR FOR NEW WIRING INSPECTION
10/20/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*UPGRADES NOW REQUIRE TWO GROUND RODS 6' APART IN ADDITION TO WATER & GAS BONDS.
SCRAPE PAINT OF LOCATION WHERE GAS BOND CONNECTED
PERMIT FOR NEW WIRING IN PANEL MUST BE OBTAINED AND INSPECTED-NEW WIRING GOING DOWN 1" EMT INTO BASEMENT, DRYER CIRCUIT, CIRCUITS 19 & 20 MARKED SPARES BUT HAVE NEW WIRING.
PANEL REQUIRES SIEMANS BREAKER AS PER INSIDE LABEL