Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 10/20/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/19/2005 | ELECTRIC - UNDERGROUND | Denied | UPGRADES NOW REQUIRE TWO GROUND RODS 6'APART IN ADDITION TO WATER & GAS BONDS SCRAPE PAINT OF LOCATION WHERE GAS BOND CONNECTED PERMIT FOR NEW WIRING IN PANEL MUST BE OBTAINED AND INSPECTED-NEW WIRING GOING DOWN 1" EMT INTO BASEMENT, DRYER CIRCUIT, CIRCUIT 19-20 MARKED SPARES BUT HAVE NEW WIRING PANEL REQUIRES SIEMANS BREAKER AS PER INSIDE LABEL. |