Permit: T05EL02086

Parcel: 135052510

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/16/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*OK TO CLEAR SER. UPGRADE
CALL FOR FINAL INSPECTION WHEN CUTOVER HAS BEEN COMPLETED W/T.E.P & BRANCH CIRCUIT HAVE BEEN CONNECTED TO THE NEW SERVICE EQUIPMENT
11/07/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*DRYWALL SCREWS NOT ACCEPTABLE FOR SERVICE EQUIP. RISER SUPPORT
CLEAN WATER PIPE AT BOND CLAMP ATTACHEMENT
INSTALL 2ND ROD PER 250 N.E.C
BOND GAS PIPING PER N.E.C
DRIVE RODS FLUSH OR BELOW FINISHED GRADE PER N.E.C
SECURE GROUNDING ELECTRODE CONDUCTOR AT WALL & SLAB
NEED NAME & LIC. # OF ELECTRICAL CONTRACTOR DOING THIS JOB AND IT NEEDS TO BE LISTED ON THEIS PERMIT PRIOR TO NEXT INSPECTION
INSTALL BUBBLE TYPE COVER FOR OUTLET BELOW PANEL