Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*OK TO CLEAR SER. UPGRADE CALL FOR FINAL INSPECTION WHEN CUTOVER HAS BEEN COMPLETED W/T.E.P & BRANCH CIRCUIT HAVE BEEN CONNECTED TO THE NEW SERVICE EQUIPMENT |
|
| 11/07/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*DRYWALL SCREWS NOT ACCEPTABLE FOR SERVICE EQUIP. RISER SUPPORT CLEAN WATER PIPE AT BOND CLAMP ATTACHEMENT INSTALL 2ND ROD PER 250 N.E.C BOND GAS PIPING PER N.E.C DRIVE RODS FLUSH OR BELOW FINISHED GRADE PER N.E.C SECURE GROUNDING ELECTRODE CONDUCTOR AT WALL & SLAB NEED NAME & LIC. # OF ELECTRICAL CONTRACTOR DOING THIS JOB AND IT NEEDS TO BE LISTED ON THEIS PERMIT PRIOR TO NEXT INSPECTION INSTALL BUBBLE TYPE COVER FOR OUTLET BELOW PANEL |