Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/07/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*GROUNDING ELECTRODE TO BE AS CLOSE AS PRAC?? TO SERVICE 250.50 ANITOXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS RISER SUPPORTS TO BE SECURED TO STRUCTURE 1/4" MINIMUM HARDWARE. SUPPORT CONDUIT BELOW PANEL AND PROTECT FROM CORROSION PROTECT CABLES IN BACK OF GUTTER FROM SHARP METAL EDGES. |