Permit: T05EL02034

Parcel: 106042570

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/11/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/06/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*100 AMP SERVICE DISCONNECT HAS A # 12 ROMEX DOUBLE LUGGED AT BOTTOM OF FUSE, REMOVE # 12 WIRE FROM DISCONNECT, ALSO # 12 ROMEX CANNOT BE RUN OUTDOORS- SAME FOR UNIT "C" OR #3