Permit: T05EL02025

Parcel: 119044610


Addresses:

3625 S 7TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
10/12/2005 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
10/04/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*INSTALL ADDRESS NUMBERS ON ELECTIC SERVICES FOR ID. MUST BE PERMANENT LABLES, SCREWED OR RIVITED TO COVERS
DEAD FRONT COVER MISSING ON BREAKER PANELS OUTSIDE.
SMOKE DETECTOR IN BEDROOM TO LOW MUST BE AT 6" TO 12" BELOW CEILING
RE SUPPORT RISER CONDUITS AT FRONT BLD'S BRICKS ARE PULLING OUT OF WALL.