Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :$ | |
| 10/04/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*AN ADDRESS LABEL IS NEEDED WHERE IS NEW GROUNDING ELECTRODE SYSTEM, GAS & WATER BONDS A BOND BUSHING IS NEEDED FOR SERVICE NIPPLE ANTI OXIDE COMPOUND IS NEEDED FOR ALL ALUMINUM CONDUCTORS A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS. CORRECTLY ID UNGROUNDED CONDUCTORS PLEASE VERIFY PERMIT FOR NEW A/C TIGHTEN ALL TERMINATIONS AT LUGS |