Permit: T05EL01997

Parcel: 117091740


Addresses:

1034 S HERBERT AV

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/07/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*OK TO CLEAR INC 1034 S HERBERT
WHAT ABOUT 1036?
11/01/2005 ELECTRIC - FINAL Denied 1) PROVIDE REQUIRED BUSHINGS FOR ALL FEEDERS
2) SECURE BACK FED BREAKERS WITH SCREW OR HOLDOWNS
3) DRIVE GROUND RODS FLUSH
4) FLOAT (INSULATE) NEUTRALS FROM DISCONNECTS ALL THE WAY INTO SUB PANELS (NO BAR NEUTRAL)
5) GROUND SUB PANELS WITH MINIMUM #10 CU EQUIPMENT GROUND
6) TIGHTEN ALL SCREWS AND LOCK NUTS