Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK TO CLEAR INC 1034 S HERBERT WHAT ABOUT 1036? |
|
| 11/01/2005 | ELECTRIC - FINAL | Denied | 1) PROVIDE REQUIRED BUSHINGS FOR ALL FEEDERS 2) SECURE BACK FED BREAKERS WITH SCREW OR HOLDOWNS 3) DRIVE GROUND RODS FLUSH 4) FLOAT (INSULATE) NEUTRALS FROM DISCONNECTS ALL THE WAY INTO SUB PANELS (NO BAR NEUTRAL) 5) GROUND SUB PANELS WITH MINIMUM #10 CU EQUIPMENT GROUND 6) TIGHTEN ALL SCREWS AND LOCK NUTS |