Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*BUSHINGS REQUIRED AT 1 1/2" CONDUIT TERMINATIONS USE BOND BUSHING AT SUB PANEL CONNECTOR NOT SEATED INTO KO CORRECTLY GROUNDING ELECTRODE SYSTEM REQUIRED TO TIE INTO SUB PANEL GROUND BAR AT MAIN HOUSE.SERVICE MTD AT BACK APT. COLER CODE FEEDER EQUIP. GROUND GREEN. ALL CIRCUIT BREAKERS MUST BE THE SAME BRAND AS PANEL MANUF. UNDERGROUND CONDUIT BETWEEN SERVICE AND SUB PANEL OK TO COVER SEPARATE NEUTRALS & GROUNDS AT SUB PANEL |