Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL01961
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*SERVICE PANELS TO HIGH( 6 TOTAL) TENANTS MUST HAVE ACCESS TO SERVICE OVER CURRENT DEVICES IN CASE OF EMERGENCY. ALSO THE NEC. STATES THAT HIGHEST BREAKER NOT TO EXCEED 6'7" 240-24 (B) 404-8 OBTAIN SERVICES OF LICENSED CONTR TO RELOCATE SERVICE TO CODE COMPLIANCE AS REQUIRED BY NEC. |
|
| 09/29/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : APPEARS THAT EXTERIOR REMODEL IN PROGRESS-SERVICE PANELS TO HIGH( APPROX 8' -9') MUST BE WITHIN REACH OF TENANTS. ALSO THE ENCLOSURE FOR RISER TERMINATION NOT SUPPORTED. The wiring is not complete or does not comply with code.| 245* |