Permit: T05EL01960

Parcel: 126062220


Addresses:

4050 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/05/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/02/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/27/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* AC CONDUCTORS TO BE AT 18" PER 300.5
PLEASE VERIFY GROUNDING ELECTRODE SYSTEM AS NEAR AS POSSBILE TO SERVICE.
RISER SUPPORT TO BE SECURED TO STRUCTURE 1/4" HARDWARE MINIMUM.
AN APPROVED SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PART.
FILL UNUSED OPENING IN BAKC OF PANEL WITH NOT-COMBUSTIBLE PRODUCT.
CANNOT DETERMINE IF AC CONDUCTORS ARE UNDERGROUND LISTED WIRE.
PLEASE VERIFY GAS & WATER BONDING.
PROTECT CABLE ENTERING CONDUIT FROM SHARP METAL EDGE
WHERE IS DRYER CIRCUIT.