Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/02/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/27/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* AC CONDUCTORS TO BE AT 18" PER 300.5 PLEASE VERIFY GROUNDING ELECTRODE SYSTEM AS NEAR AS POSSBILE TO SERVICE. RISER SUPPORT TO BE SECURED TO STRUCTURE 1/4" HARDWARE MINIMUM. AN APPROVED SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PART. FILL UNUSED OPENING IN BAKC OF PANEL WITH NOT-COMBUSTIBLE PRODUCT. CANNOT DETERMINE IF AC CONDUCTORS ARE UNDERGROUND LISTED WIRE. PLEASE VERIFY GAS & WATER BONDING. PROTECT CABLE ENTERING CONDUIT FROM SHARP METAL EDGE WHERE IS DRYER CIRCUIT. |