Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 10/10/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*COVER TO BE BUBBLE TYPE PER 406.8 ALL ALUMINUM CONDUCTORS TO SUE ANTIOXIDE COMPOUND. WHERE IS GROUNDING EQUIPMENT CONDUCTOR? OTHER ITEMS COMPLETED |
|
| 10/06/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*TIGHTEN LOOSE FITTINGS POOL RECEPTACLE & SWITCH TO BE WEATHER PROOF COVER AS PER 406.8 BREAKER AMPACITY TO MATCH CONDUCTOR SIZE ANTIOXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS LB COVER FOR SERVICE CONDUCTORS TO BE LOCKABLE SMOKE DETECTORS NEEDED FOR BEDROOMS WE HAVE 3 WIRE RECEPTICALS ON A 2 WIRE SYSTEM UNGROUNDED WE HAVE EXPOSED CONDUCTORS IN KITCHEN. |