Permit: T05EL01950

Parcel: 134172360


Addresses:

754 S MARVIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/14/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/12/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
10/10/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*COVER TO BE BUBBLE TYPE PER 406.8
ALL ALUMINUM CONDUCTORS TO SUE ANTIOXIDE COMPOUND. WHERE IS GROUNDING EQUIPMENT CONDUCTOR?
OTHER ITEMS COMPLETED
10/06/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*TIGHTEN LOOSE FITTINGS
POOL RECEPTACLE & SWITCH TO BE WEATHER PROOF COVER AS PER 406.8
BREAKER AMPACITY TO MATCH CONDUCTOR SIZE
ANTIOXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS
LB COVER FOR SERVICE CONDUCTORS TO BE LOCKABLE
SMOKE DETECTORS NEEDED FOR BEDROOMS
WE HAVE 3 WIRE RECEPTICALS ON A 2 WIRE SYSTEM UNGROUNDED
WE HAVE EXPOSED CONDUCTORS IN KITCHEN.