Permit: T05EL01948

Parcel: 136252920


Addresses:

6700 E FAYETTE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/10/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* TEP TO RELOCATE SERVICE DROP PER CUSTOMER
09/26/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* INSTALL GROUND RODS ( 2 ??) 8' X 5/8'' PER N.E.C ART . 250. USE ANTIOXIDATION PASTE ON ALUM TERMINATIONS. USE CUTLER HAMMER BREAKERS FOR CUTLER HAMMER PANEL. INSTALL METAL ADDRESS TAG PER T.E.P. INSTALL GAS BOND. NOTE: PER ART 680 N.E.C O.H LINES NEED TO BE A MIN. OF 22' AWAY FROM WATERS EDGE.