Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* TEP TO RELOCATE SERVICE DROP PER CUSTOMER | |
| 09/26/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL GROUND RODS ( 2 ??) 8' X 5/8'' PER N.E.C ART . 250. USE ANTIOXIDATION PASTE ON ALUM TERMINATIONS. USE CUTLER HAMMER BREAKERS FOR CUTLER HAMMER PANEL. INSTALL METAL ADDRESS TAG PER T.E.P. INSTALL GAS BOND. NOTE: PER ART 680 N.E.C O.H LINES NEED TO BE A MIN. OF 22' AWAY FROM WATERS EDGE. |