Permit: T05EL01942

Parcel: 106020950

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Permit Number - T05EL01942

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Denied

Date Description Inspector Results Comments
09/23/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999* 1. SERVICE DISCONNECT BY MH NEEDS TO BE SUPPORTED. 2. MUST ALSO HAVE ONE GROUND ROD WITH A # 6 COPPER FROM GROUND ROD TO SERVICE DISCONNECT. 3. NO BREAKER PANEL IN MH. 4. NO FEEDER TO DISCONNECT OR PLUG. 5. FUSE PULL OUT AT SERVICE BROKEN. OBTAIN THE SERVICES OF A LICENSED ELECTRICAL CONTRACTOR TO REPAI & RECALL. 6. PAINT # ON DISCONNECT.