Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2005 | ELECTRIC - FINAL | Approved | ||
| 12/14/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* GATE LOCKED -- RECALL INSPECTION |
|
| 09/16/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE IS INADEQUATE, NEEDS TO BE UPGRADED A. INPROPERLY GROUNDED, WIRE CUT B. INPROPER SPLICES C. IMPROPER FEED TO OLD SWITCH, OLD SWITCH CAN NOT BE USED AS J-BOX 2) MC CABLE NOT TO BE RUN OUTDOORS 3) ALL DEVICES TO BE INSTALLED 4) SMOKE DETECTORS IN BEDROOMS TO BE WORKING NORTH BED ROOM MISSING 5) REPAIR OUTSIDE PORCH LIGHT - NEEDS BOX BETWEEN WIRE AND FIXTURE 6) SOUTH WEST BEDROOM PROPERLY INSTALL RECEPTABLE ON WALL PROTECT WIRING 7) KITCHEN FIXTURE REMOVE OR REPLACE 8) HOUSE ONLY HAS TWO 20 AMP CIRCUITS INSUFFICIENT FOR ENTIRE HOUSE HOUSE IS VACANT GUGGEST YOU OBTAIN SERVICES OF OF ELECTRICIAN |