Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/23/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. #6 IS TOO SMALLL FOR GROUNDING ELECTRODE CONDUCTOR FOR 200 AMP SERVICE. 2. INSTALL WATERBOND AT INTERIOR SIDE OF DIELECTRIC UNION AT WATER PIPE. 3. GROUNDING ELECTRODE CONNECTION AT NORTH GROUND ROD IS INCORRECT ( TERMINATE LIKE YOU DID THE SOUTH ROD ON OPPOSITE SIDE OF BOLT. 4) DRIVE GROUND RODS FLUSH OR BELOW FINISHED GRADE 5. INSTALL 3/4" CONDUIT STRAP AT CONDUIT ON SIDE OF PANEL. 6. INSTALL ANTI OXIDATION PASTE ON ALUM. CONDUCTORS 7) INSTALL 3/4" BOND BUSHING AT CONDUIT ENTRY DUE TO REDUCING WASHERS. |