Permit: T05EL01903

Parcel: 134243280


Addresses:

1001 S COLGATE DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/27/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/23/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1. #6 IS TOO SMALLL FOR GROUNDING ELECTRODE CONDUCTOR FOR 200 AMP SERVICE. 2. INSTALL WATERBOND AT INTERIOR SIDE OF DIELECTRIC UNION AT WATER PIPE. 3. GROUNDING ELECTRODE CONNECTION AT NORTH GROUND ROD IS INCORRECT ( TERMINATE LIKE YOU DID THE SOUTH ROD ON OPPOSITE SIDE OF BOLT. 4) DRIVE GROUND RODS FLUSH OR BELOW FINISHED GRADE 5. INSTALL 3/4" CONDUIT STRAP AT CONDUIT ON SIDE OF PANEL. 6. INSTALL ANTI OXIDATION PASTE ON ALUM. CONDUCTORS 7) INSTALL 3/4" BOND BUSHING AT CONDUIT ENTRY DUE TO REDUCING WASHERS.