Permit: T05EL01893

Parcel: 113083100

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/22/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK TO CLEAR
09/21/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED MAIN BREAKER AT INDIVIDUAL SUB PANELS (SEPERATE BLDGS)
2) GROUNDING ELECTRODE SYSTEM REQUIRED AT SEPERATE BLDGS
3) INSTALL GFI RECEPTACLE AT OWNERS PANEL
4) ARC FAULT ?
5) INSTALL BOND BUSHING AT OWNERS PANEL AND TERMINATE CONDUCTORS