Permit: T05EL01889

Parcel: 11204380A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL01889

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/14/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE GROUNDING ELECTRODE-WATER BOND IS NOT CONNECTED AT THE ELECTRICAL SERVICE (NEED THIS REPAIRED PRIOR TO THE NEXT INSPECTION)
2) INSTALL CORRECT SIZED FUSES AT FUSE PANEL
3) NEED PERMIT FOR WATER HEATER AND FINAL PRIOR TO ELECTRICAL CLEARANCE TO TEP (INSTALL ? ? CRIMP CONNECTOR FOR STRANDED GROUNDING CONDUCTOR
CONNECTION AND WIRE W.H. PER N.E.C.